Electric Power System EquipmentOperation And Maintenance运行与维护
2018年第7期
2018 No.7
变电运行跳闸故障的处理技术分析
贾 峰
(国网营口供电公司,辽宁营口 115000)
[摘 要]电力作为现代工作生活中必不可少的能源,其重要性不言而喻,而变电运行的稳定性作为电力保证直接体现供电安全与质量。跳闸作为变电运行过程汇总最常见的故障种类,因其突发性、严重性等特点关乎着整个变电运行流程以至于整个供电系统的供电安全与质量。所以变电运行中对于跳闸的防患以及处置工作成为电力维护工作者工作中的重点方面。文章从分析变电运行期间跳闸的种类与原因入手,对相应的处理技术手段做总结和分析。[关键词]变电运行;跳闸;处理技术[中图分类号]TM73 [文献标志码]B [文章编号]1001-523X(2018)07-0151-02
Analysis of Handling Technology for Substation Operation Trip Fault
Jia Feng
[Abstract]as a necessary energy in modern work and life, the importance of electricity is self-evident, and the stability of the electric power operation, as a direct embodiment of the power guarantee, is closely related to the safety and quality of power supply. The trip is the most common type of fault in the process of substation operation. Because of its sudden and serious characteristics, the whole power supply safety and quality of the whole power supply system are related to the whole transformer operation process. So for the substation operation for the prevention and disposal of tripping work has become the focus of the work of electrical maintenance workers. Based on the analysis of the types and causes of tripping during substation operation, the paper summarizes and analyzes the corresponding processing techniques.
[Keywords]substation operation; tripping; processing technology1 变电与跳闸的相关概念
变电作为一个物理概念,指通过多种手段将电器额定电压进行升压或降压变化的操作。在现实工作中,由于在发电系统内使用的发电机组的额定电压各不相等,同时,常规的输电各阶段存在不同等级的电压需求,而配电系统中配电电压也存在一定的波动,这就要求通过变压操作实现标准固定电压下的各系统间的链接工作。变电作为协调发电、输电、配电等环节中电压的重要环节,其自身是一个机制复杂的系统。
由于变电系统内部机制相互联系,任一部分出现相关情况就会导致电路断开,即出现跳闸故障。究其原因,是因为在发电、配送电过程中,为了保证整个供电系统的安全,变电系统中会安装继电保护装置,当出现突发事故时,机电保护装置被事故出现的短路电流冲击而自动断开,形成系统内的短路,出现跳闸现象。这种保护机制可以将故障损失控制在一个最小范围内,从而最大限度保护其他相关电力设备。2 变电系统中常见的跳闸故障原因
2.1 硬件问题导致跳闸故障
线故障与连线故障。由于主变三侧结构比较复杂,判断主要的故障点位置必须通过对相关设备情况与保护动作信号如对于主变瓦斯保护动作、差动保护动作的具体分析来寻找和判断故障点。
2.2 线路开关跳闸的故障
由于变电系统的运行过程中,因其自身承担在电网中进行相关变压的工作,所以需要按照网状布置大量的电路。而相应的特殊变压装置由于保证运行安全、运行效率等考虑都会安排在远离生活区,在偏远地区进行架设。这就对检修维护工作的开展造成了困难,一方面,范围广、距离远的输电网络变电系统在检修过程中在工程量上对于检修人员来说是一种挑战;另一方面,大量地处偏远地区的重要变电装置一旦出现问题不能第一时间进行处理。另外,一些类似条幅、彩带、风筝等民用悬空设施与配电系统之间会发生绕线问题、鸟类在电线上休息会导致温度升高产生短路等都是线路开关跳闸故障产生的几大原因。
2.3 设备检查问题引发的跳闸故障
变电系统中,根据故障发生种类,较为常见的跳闸故障主要分为:单线路开关的跳闸故障、主变单侧开关的跳闸故障、主变三侧开关的跳闸故障。
(1)单线路开关的跳闸故障:变电系统中,各个线路是构成系统间部件连接的主要形式和内容。其中相关特殊承载性质的单电路由于其在系统中发挥重要作用和关键功能,发生短路的几率要远高于其他电路。引起单线路开关跳闸故障的原因分外界原因与设备自身原因2个方面,外界原因诸如自然灾害、施工影响,设备自身原因主要包括线路断开、短路、相关接地连接处理不良、设备自身承载电压过高、设备自身线路或部件质量问题等。
(2)主变单侧开关的跳闸故障:主变后备动作中单侧开关发生跳闸,这种跳闸故障出现的原因主要是跳闸的一侧出现电力过流现象,使得在主动保护系统开启,出现自动跳闸以保护系统部件。另外在单侧开关的跳闸故障也与人为开关、线路中母线系统出现故障导致越级跳闸等原因有关。
主变三侧开关的跳闸故(3)主变三侧开关的跳闸故障:
障主要原因是主变压器侧中动区、内部或者是低压侧发生出
由于变电系统保障工作的开展可以帮助变电设备持续安全的进行工作,所以定期对于变电系统进行运行维护就成为一个必要的环节。但是在实际检修过程中,由于变电系统中的设备种类多、数量大,检修工作人员在面对一个庞杂的变电系统时,无法做到面面俱到,对于相关检修具体工作的开展也很难做到认真检修。检修工作效率无法保证,自然会在变电系统运行的过程中出现隐患,这也是出现跳闸故障的一个主要原因。
2.4 外界环境因素造成的跳闸故障
变电系统严密复杂,在整个电力系统中又起到重要的作用,通常变电系统在设计和架构时都会考虑到环境因素对其自身性能的影响,而具体在现实情况中,各种现实环境中恶劣因素对变电的系统的影响还是严重的。比如恶劣的气象条件如强风、暴雨、雷击等都会影响变电系统的正常运行,有时过于恶劣的极端天气还会破坏变电设备。3 跳闸的故障处理技术分析
3.1 对于硬件跳闸的故障处理技术分析3.1.1 对于单线路跳闸的处理
2018.7 电力系统装备丨151
2018年第7期
2018 No.7
Operation And Maintenance运行与维护
Electric Power System Equipment电力系统装备
火电厂继电保护装置的应用安全分析
蒋 桦
(中电建湖北电力建设有限公司,湖北武汉 430030)
[摘 要]在社会经济飞速发展的当今时代,电力系统取得了突飞猛进的发展,继电保护装置更是实现了测量、保护、控制、网络化、计算机化、人工智能化以及数据通讯一体化的发展。因此,在火电厂的继电保护系统中,越来越多的新理念以及新技术得到了广泛的应用,因此,继电保护调试工作者也面临着更大的挑战,需要对新的科学技术进行合理的掌握,对自身的专业技能不断的提高,从而实现继电保护的可靠性,这样也就对电网的安全运行提供了良好的保障。文章对火电厂的继电保护装置进行了全面系统的分析,以达到提高其应用安全性的目的。[关键词]火电厂;继电保护装置;应用安全[中图分类号]TM621;TM774 [文献标志码]A [文章编号]1001-523X(2018)07-0152-02
Analysis of the Application Safety of Relay Protection Device in
Thermal Power Plant
Jiang Hua
[Abstract]In the current era of rapid social and economic development, the power system has also made rapid development, and for the relay protection device, it has realized the development of measurement, protection, control, network, computerization, artificial intelligence and the integration of data communication. Therefore, in the relay protection system of thermal power plants, more and more new ideas and new technologies have been widely used. Therefore, the debugging workers of relay protection are facing more challenges. It is necessary to grasp the new science and technology reasonably and improve their professional skills and ability, so as to realize the relay protection. The reliability of the protection. This will also provide a good guarantee for the safe operation of the power grid. This paper is a comprehensive and systematic analysis of the relay protection device of the power plant, so as to improve its application security.
[Keywords]thermal power plant; relay protection device; application safety本文对火电厂继电保护装置进行研究,并且对运行过程中存在的常规故障提出了解决的措施。1 火电厂的继电保护装置
1.1 对发电机进行的保护
首先进行对发电机的差动保护,因为发电机有不同的位置以及不同的连续方式,所以应该根据实际的情况选择不完
在进行单线路跳闸故障处理上,需要根据故障产生的不同情况,对系统内整体线路进行全面检查。在排除线路故障之后,需要重点对消弧线圈与线路控制开关2处跳闸故障的重点位置进行重点检查。检查工作主要从动力保险接触情况中是否存在异常来判断故障点,并注意排除主变低压侧的过载保护问题。
3.1.2 主变单侧开关跳闸的处理
主变单侧开关跳闸主要有3个原因:母线线路故障、开关发生误动以及开关发生保护动作据动。以主变低压侧跳闸为例,如果主变低压侧出现跳闸现象,必须对主变以及线路双层保护机制进行排查,具体处理方法为:首先隔离故障位置,恢复其他部分的供电。若主变低压侧出现过流保护,则须将母线的全部负荷开关先进行脱离,再根据线路开关相应顺序依次拉合。
3.1.3 主变三侧开关跳闸的处理
在分析主变三侧开关跳闸原因时,由于主变三侧结构比较复杂,要想判断主要的故障点位置,就必须通过对相关设备情况与保护动作信号如对于主变瓦斯保护动作、差动保护动作的具体分析来寻找和判断故障点。所以在进行相关处理时的技术分情况处理:若跳闸故障伴随着变压器的瓦斯保护动作产生,那么可以基本断定故障原因发生在二次回路或变压器内部,需对相应部分进行重点检查;若呼吸器无喷油现象同时二次回路并没有出现短路或接地情况,则需要对变压器变形、起火等问题进行重点检查;若短路伴随着差动保护,则需要对主变压器油色与油位进行检查,并检查套管和瓦斯
152丨电力系统装备 2018.7
继电器等其他部件;若瓦斯继电器中发现还有相关气体留存,则需要对于气体的可燃性进行检验和判断。
3.2 常见线路跳闸故障的处理
对于变电运行中比较常见的线路跳闸故障的处理主要需要在跳闸故障出现后,须进行开关保护检查,观察录波装置的动作,记录相关数据与情况,将检查的结果与故障信息整理后向值班工作人员汇报,通过值班人员的分析与判断做线路的巡检工作规划和执行方法。在巡检工作中,检修人员还需对跳闸开关进行检查,观察开关是否有外观、操作机构、保护装置有损坏、失灵、勿动等情况,同时检查相关的后台信号,查看接收情况与信号干扰情况,排除相关故障。
3.3 外界因素造成跳闸故障的处理
外界因素对于变电的影响主要通过主动预防来避免。主要处理方法可以通过日常运维中加大对于高压输电线路的排查,在恶劣天气来临前主动做好电网设施加固、增加输电杆、塔强度等措施,最大限度减小以天气为主的外界因素对于 变电的影响。
综上所述,作为输电过程中的重要系统部分,变电系统跳闸故障的种类、涉及的技术要点、相应的处理方式比比皆是,针对故障特点,通过科学的分析故障,并通过相应的技术手段进行处理,对于降低跳闸故障带来的不利影响,促进电业行业发展有着积极的意义。
参考文献
[1] 郑志祥.变电运行跳闸故障处理技术应用刍议[J].科技与创新,2014(16):54.
因篇幅问题不能全部显示,请点此查看更多更全内容